Home
Up

   

 Twin Stream Regulator Module Specification and Sizing 

Regulator modules for use with above ground tanks

Tank size in litres

Number of tanks

Offtake capacity in kW/h

Module capacity in kW/h

1st stage module part number

Single cut module part number

2000

1

187

550

102651

102715

2

374

3

561

4000

1

269

2

538

3

807

1614

 

102652

102716

4

1076

5

1345

6

1614

8000

1

463

550

102651

102715

2

926

1614

102652

102715

3

1389

24000

1

1046

2920

102714

N/A

2

2092

Regulator modules for use with underground tanks

Tank size in litres

Number of tanks

Offtake capacity in kW/h

Module capacity in kW/h

1st stage module part number

Single cut module part number

2000

1

187

550

102675

102712

2

374

3

561

4

269

5

538

6

807

4000

1

1076

2

1345

3

1614

4

463

5

926

1614

102676

102713

6

1389

Part numbers and thread sizes

Part number

Capacity

Description

Inlet thread

Outlet thread Outlet pressure

102675

40kg/h 1st stage underground 1/2" NPT 3/4" BSPT 0.8 bar
102676 120kg/h 1st stage underground 3/4" NPT 1” BSPT 0.8 bar
102712 40kg/h Single cut underground 3/4" NPT 2” BSPT 75 mbar

102713

120kg/h Single cut underground 3/4" NPT 2” BSPT 75 mbar
102714 210kg/h 1st stage single stream above ground 1” NPT 1” BSPT 0.8 bar
102715 40kg/h Single cut above ground 3/4" NPT 2” BSPT 75 mbar
102716 120kg/h Single cut above ground 3/4" NPT 2” BSPT 75 mbar
102651 40kg/h 1st stage above ground 1/2" NPT 3/4" BSPT 0.8 bar
102652 120kg/h

1st stage above ground

3/4" NPT 1” BSPT 0.8 bar